Overheated Wire at the Circuit Breaker

Overheated electrical wiring and components are an indication of a serious electrical problem and should promptly be evaluated by a professional.

This picture shows an overheated wire at the circuit breaker.  Overheated electrical wiring and components should promptly be evaluated by a professional.  Overheating is an indication of a serious electrical problem and may lead to a fire.

Call for an inspection today!

(480) 503-2611
TOLL FREE:  1-888-THE-WERX

Or Schedule Online!

Comments

3 responses to “Overheated Wire at the Circuit Breaker”

  1. Bob Johnson Avatar
    Bob Johnson

    There are two questions here.
    Why did it overheat? Clearly a bad connection at the breaker. Either the terminal or contacts within the breaker overheated. If an overload occurred, all the wire would have been overheated. If the circuit can be monitored, simply clean and retighten the terminal. If not, replace the breaker.
    Why a red wire? It may be a simple two wire circuit installed with a red wire. However it should be checked to see if this is part of a multiwire circuit. If so it deserves a multipole breaker.

  2. Abdulgader Avatar
    Abdulgader

    can we get a good tighten on the breaker with the over head wiers? I think we break the termials, or we will have a lose concctions so we will have an over heat.

  3. Rusty Bennett Avatar
    Rusty Bennett

    This is a SquareD panel, one of the best in the business. I think the scorching of the wire indicates localized heating at the connection point, indicating a poor connection on a relatively heavy load. The breaker apparently was not tripping, so the load is likely within specs, but after repair, it should be tested with a clamp on ammeter or a current recorder if intermittent. The breaker should definitely be replaced as damage has likely occurred to it as well. A 2P breaker would only be required if the load is 2 or 3 phase or if the load supplies meet the conditions of a multi-wire circuit, especially if a neutral is connected to pass through a receptacle rather than a piggy back connection. That is worth verifying.